Fero Header Left Fero Header Right
Fero background slice SIDE MOUNTING RAP-TIE
PRODUCTS
System  |  Description  |  Design Loads & Deflections  |  Notes
Specification Guidelines  |  Installation Procedure - Animated
spacer
  SIDE MOUNTING RAP-TIE NOTES

(i) The design values reflect both the windward and leeward capacity of the Side Mounting Rap-Tie system, with the governing values listed.

(ii) The tie system recommended design load value was formulated using working stress design following the procedures of CSA CAN3-A370-M94 ?Connectors for Masonry?, ACI/ASCE/TMS/518 and U.B.C. The value has been reduced to account for test result variation, and reflect a factor of safety of 2.25 (i.e., 75% of 3.0), as per Table 3 (A370).

(iii) The allowable mortar pull-out or push-out design load for the V-Tieª embedded at the centerline of 90 mm (3.5?) brick veneer utilizing Type M, S or N mortar, exceeds or equals the recommended design load listed above.

(iv) The above design values relate to the capacity of the FERO tie components. Compatible fasteners capable of resisting the design load must be selected.

(v) The above design values are based on test results utilizing a 76 mm (3?) cavity (25 mm [1?] air apace). No insulation or drywall was used. Note that for smaller cavity widths and/or with the addition of insulation sheathing providing lateral tie support, increased tie system design loads and reduced tie system deflections may be realized.

(vi) Maximum recommended spacing reflects the maximum allowable by CSA-A370-94, ACI/ASCE/TMS/518 and U.B.C. For stud construction, every vertical stud should contain ties. Design will ultimately govern spacing.

 

 
     
spacer
spacer

[ DOWNLOAD PRINT VERSION ]

Canadian Patent No 4,869,043
Other Patents Pending
©2000-2007 Fero CorporationFERO Engineered Masonry Connectors