| |
PAC-TIE NOTES
| (i) |
The design values reflect both the windward and leeward capacity of the Pac-Tie system, with the governing values listed.
|
| (ii) |
The Pac-Tie system recommended design load values were formulated using working stress design following the procedures of CSA CAN3-A370-04 Connectors for Masonry, ACI/ASCE/TMS/518 and U.B.C. The values have been reduced to account for test result variation, and reflect a factor of safety of 2.25 (i.e., 75% of 3.0), as per Table 3 (A370).
|
| (iii) |
The allowable mortar pull-out or push-out design load for the V-Tie embedded at the centerline of 90 mm (3.5) brick veneer utilizing Type M, S or N mortar, exceeds or equals the recommended design loads listed above.
|
| (iv) |
For the Pac-Tie tests, protected drywallconsisted of Perma-Barrier (W.R. Grace) adhered to 12.7 mm (0.5) drywall, which satisfies the proposed tie attachment definition and detail to be included in the next revision of CSA CAN3-A370-04, ACI/ASCE/TMS/518 and U.B.C. Note that this detail is not recommended for use in high humidity buildings such as swimming pools, etc.
|
| (v) |
The above design values relate to the capacity of the Pac-Tie components. Compatible fasteners capable of resisting the design loads must be selected.
|
| (vi) |
The above design values are based on test results utilizing the V-Tie located at the AB-Clip centerline, and a 100 mm (4) cavity. No insulation was used. Note that for smaller cavity widths and/or with the addition of insulation sheathing providing lateral tie support, increased tie system design loads and reduced tie system deflections may be realized. |
| (vii) |
Maximum recommended spacing reflects the maximum allowable by CSA-A370-04, ACI/ASCE/TMS/518 and U.B.C. For stud construction every vertical stud should contain ties. Design will ultimately govern spacing. |
|
|
| |
|
|
|
[ DOWNLOAD
PRINT VERSION ]
Patents Pending
©2000-2006 Fero Corporation

|