| CAT-TIE DESIGN
Engineering evaluation is required if the Cat-Tie connector
provides support for larger tributary areas than the standard
veneer requirements outlined by CSA CAN3-A370-04, ACI/ASCE/TMS/518
and U.B.C.
For example, if the connector is used to fasten a concrete
block wall to steel columns spaced at 6,000 mm (20') on center,
and the design wind load is 1.0 kPa (0.145 psi), then the
lateral load applied to the columns by the block wall will
be 6.0 kN/m (411 lb/ft). Thus, the spacing of the Cat-Tie,
the fastening of the AB-Clip to the steel
member, and the embedment of the V-Tie™ into the masonry wall need
to be evaluated.
Considering the lateral load of 6.0 kN/m (411 lb/ft) and the recommended design load of the Cat-Tie of 1.50 kN (336 lbs), a Cat-Tie is required every 250 mm (10") along the column (i.e., 1.50 kN ÷ 6.0 kN/m [336 lbs ÷ 411 lb/ft x 12"/ft]). The connection of the AB-Clip to the structural steel column, and the connection of the V-Tie™ into the masonry wall must also be evaluated. As previously mentioned, bending the legs of the V-Tie™ into the cores and grouting the wall at such locations will provide for increased pull-out capacity. |